An office building is served by an air-cooled chiller currently operating at 115 tons (404.5 kW). The measured chilled water supply temperature is 43°F (6.1°C), and the measured chilled water return temperature is 57°F (13.9°C). What is the estimated chilled water flow rate through the chiller? A. 172 gpm (10.9 L/s) B. 197 gpm (12.4 L/s) C. 212 gpm (13.4 L/s)

User WebArtisan
by
5.3k points

1 Answer

1 vote

Answer:

B.197 gpm and 12.4 L/s

Step-by-step explanation:

Given that

Load Q = 404.5 KW

Water inlet temperature= 6.1 °C

Water outlet temperature= 13.9°C

We know that specific heat for water


C_p=4.187\ (KJ)/(kg.K)

Now from energy balance


Q=\dot{m}C_p\Delta T

by putting the values


Q=\dot{m}C_p\Delta T


404.5=\dot{m}* 4.187(13.9-6.1)


\dot{m}=12.38\ (kg)/(s) (1 Kg/s = 15.85 gal/min)

We can say that


\dot{m}=196.31\ (gal)/(min)

We know that


\dot{m}=\rho* volume\ flow\ rate

12.38=1000 x volume flow rate


volume\ flow\ rate\ = 12.38* 10^(-3)\ (m^3)/(s)

So

volume flow rate = 12.38 L/s

So the option B is correct.