64.2k views
0 votes
A battery with a nominal voltage of 200-V with a resistance of 10 milliohms to be charged at a constant current of 20 amps from a 3-phase semi-converter with a 220-V (line-to-line) Y-connected 60 Hs supply. Determine:

a. The firing angle of the thyristors for the charging process.
b. The displacement power factor and the supply power factor.

1 Answer

3 votes

Answer:

a) ( ∝ ) = 69.6548

b) supply power factor = 0.6709

displacement power factor = 0.8208

Step-by-step explanation:

Given data:

Nominal voltage ( E ) = 200-V

resistance (r) = 10 milliohms

constant current ( I ) = 20 amps

Phase ; 3-phase

semi-converter with 220-v ( line-to-line ) , 220√2 ( phase voltage )

frequency ; 60 Hz

a) determine the firing angle of thyristors

Vo = E + I*r

= 200 + 20*10*10^-3

= 200.2 v

attached below is the remaining part of the solution

firing angle of thyristors for charging process ( ∝ ) = 69.6548

b) determine displacement power factor and supply power factor

attached below is the detailed solution

Displacement power factor ( Dpf ) = cos ( ∝ /2 ) = 0.8208

displacement power factor = g * Dpf

= 0.81747 * 0.8208 = 0.6709

A battery with a nominal voltage of 200-V with a resistance of 10 milliohms to be-example-1
User Bcr
by
7.4k points