3. A wye-connected load has a voltage of 480 V applied to it. What is the voltage dropped across each phase?

1 Answer

3 votes

Answer:


E_s = 277.13V

Step-by-step explanation:

Given


Load\ Voltage = 480V

Required

Determine the voltage dropped in each stage.

The relation between the load voltage and the voltage dropped in each stage is


E_l = E_s * \sqrt3

Where


E_l = 480

So, we have:


480 = E_s * \sqrt3

Solve for
E_s


E_s = (480)/(\sqrt3)


E_s = (480)/(1.73205080757)


E_s = 277.128129211


E_s = 277.13V

Hence;

The voltage dropped at each phase is approximately 277.13V