An air-conditioning system is to be filled from a rigid container that initially contains 5 kg of saturated liquid R-134a at 26 °C. The valve connecting this container to the air-conditioning system is now opened until the mass in the container is 0.5 kg, at which time the valve is closed. During this time, only liquid R-134a flows from the container. Presuming that the process is isothermal while the valve is open, determine the final quality of the R-134a in the container and the total heat transfer.

User Theresa
by
3.9k points

1 Answer

3 votes

Answer:

x2 = 0.5056

Qin = 22.62Kj

Step-by-step explanation: