Use LRFD and select a W10 shape for an axially loaded column to meet the following specifications: - The length is 25 feet. - Both ends are pinned and there is bracing in the week direction at a point 10 feet from the top. - The service dead load is 150 kips, and the service live load is 320 kips.

1 Answer

5 votes

Answer:

The required area of cross section = 22 inĀ²

The member size W10x77 is safe and okay

Step-by-step explanation:

Use LRFD and select a W10 shape for an axially loaded column to meet the following-example-1
Use LRFD and select a W10 shape for an axially loaded column to meet the following-example-2