An ideal vapor-compression heat pump cycle using R-134a is used to heat a house. The insidetemperature is 22°C, the outside temperature is 0°C. Saturated vapor at 2.2 bar enters thecompressor, saturated liquid leaves the condenser at 8 bar. The mass flow rate is 0.2 kg/s.

Calculate:
(a) the power input to the compressor, in kW.
(b) the coefficient of performance.

User Redanium
by
6.1k points

1 Answer

3 votes

Answer:

(a) The power input to the compressor= 3.47 KW

(b) The coefficient of performance=9.90

Step-by-step explanation:

The solution and complete explanation for the above question and mentioned conditions is given below in the attached document.i hope my explanation will help you in understanding this particular question.