An EMT raceway contains two 3-phase, 480-volt branch circuits. What minimum size THHN branch circuit conductor is required for one of the circuits when it supplies a noncontinuous load of 27 kW?

User Anette
by
4.1k points

1 Answer

1 vote

Answer:8 AWG

Explanation: 6 current carrying conductors with 2 - 3 phase branch circuits. Divide 27000 by (480v × 1.732 or square root of 3) and you get 32.46 amps. Now using the code book, divide 32.46 by the adjustment factor of 6 CCC's which is .8 and you get 40.61 amps. Now go to Table 310.16 in the 2020 NEC book and you'll see that in the 90° column that 40.61 amps is above #10 AWG so you size up to #8 AWG.