Refrigerant-134a at 1 MPa and 100 C is to be cooled to 1 MPa and 28 C in a condenser by air. The air enters at 125 kPa and 25 C with a mass flow rate of 697 kg/min and leaves at 97 kPa and 58 C. Determine the mass flow rate of the refrigerant. Assume air has a constant heat capacity determined at room temperature. Report the mass flow rate of the refrigerant in kg/min with one decimal digit, for example 95.3 or 105.6.