An air conditioner operating at steady state maintains a dwelling at 70°F on a day when the outside temperature is 99°F. The rate of heat transfer into the dwelling through the walls and roof is 30,000 Btu/h and the net power input to the air conditioner compressor is 3.3 hp.

Required:
a. Determine the coefficient of performance of the air conditioner.
b. Determine the power input required, in hp, and the coefficient of performance for a reversible air conditioner providing the same cooling effect while operating between the same cold and hot temperatures.

1 Answer

3 votes

Answer:

a) the coefficient of performance of the air conditioner is 3.5729

b)

- the power input required for a reversible air conditioner is 0.645 hp

- the coefficient of performance for the reversible air conditioner is 18.2759

Step-by-step explanation:

Given the data in the question;

Lower Temperature
T_L = 70°F = ( 70 + 460 )R = 530 R

Higher Temperature
T_H = 99° F = ( 99 + 460 )R = 559 R

Cooling Load
Q_L = 30000 Btu/h

we know that 1 hp = 2544.43 Btu/h

Net power input P = 3.3 hp = ( 3.3 × 2544.43 )Btu/h = 8396.619 Btu/h

a)

Coefficient of performance of the air conditioner;


COP_{air-condition = Cooling Load
Q_L / power P

we substitute


COP_{air-condition = 30000 Btu/h / 8396.619 Btu/h


COP_{air-condition = 3.5729

Therefore, the coefficient of performance of the air conditioner is 3.5729

b)

- Power input required ( in hp )


Q_L /
P_{required =
T_L / (
T_H -
T_L )

we substitute

30000 Btu/h /
P_{required = 530 R / ( 559 R - 530 R )

30000 Btu/h /
P_{required = 530 R / 29 R

we solve for
P_{required


P_{required = ( 30000 Btu/h × 29 R ) / 530 R


P_{required = ( 870000 Btu/h / 530 )


P_{required = 1641.5094 Btu/h

we know that; 1 hp = 2544.43 Btu/h

so;


P_{required = ( 1641.5094 / 2544.43 ) hp


P_{required = 0.645 hp

Hence, the power input required for a reversible air conditioner is 0.645 hp

- the coefficient of performance for the reversible air conditioner;


COP_{rev-air-condition =
T_L / (
T_H -
T_L )

we substitute


COP_{rev-air-condition = 530 R / ( 559 R - 530 R )


COP_{rev-air-condition = 530 R / 29 R


COP_{rev-air-condition = 18.2759

Hence, the coefficient of performance for the reversible air conditioner is 18.2759