A continuously loaded utilization equipment for a dwelling is rated at 20 amperes and is non motor operated, the branch circuit overcurrent device is not tested for continuous loading. What's the smallest branch circuit rating?

1. 20 amperes
2. 25 amperes
3. 30 amperes
4. 40 amperes

User Bromind
by
7.9k points

1 Answer

4 votes

Final answer:

The smallest branch circuit rating for a 20-ampere non-motor operated continuous load, based on safety regulations, is 25 amperes.

Step-by-step explanation:

The smallest branch circuit rating for a continuously loaded utilization equipment rated at 20 amperes that is non-motor operated and where the branch circuit overcurrent device is not tested for continuous loading is, per safety regulation, 25 amperes. Safety regulations limit continuous use to 80% of the breaker current capacity to allow for a safety margin and to prevent overheating which could lead to damage or fire. Therefore, for a 20-ampere continuous load, the breaker should be rated at least 25 amperes to handle the load safely.