A tech finds that the cad-cell is reading a very high resistance while the burner is operating. the cause could be

a. Dirtiness or sooting of the cell
b. The orange and white wires
c. Not enough primary air
d. Open the barometric damper

User Kata
by
8.4k points

1 Answer

5 votes

Final answer:

A cad-cell reading very high resistance during burner operation could be caused by dirtiness or sooting, wiring issues, insufficient primary air, or incorrect barometric damper settings, requiring maintenance by a qualified technician.

Step-by-step explanation:

If a technician finds that the cad-cell is reading a very high resistance while the burner is operating, the most likely causes include:

  • Dirtiness or sooting of the cad-cell, which obstructs the cell's ability to detect light, leading to an incorrect high resistance reading.
  • Problems with the wiring, such as damaged or deteriorated insulation on the orange and white wires, which could cause poor connections and faulty readings.
  • Insufficient primary air can lead to incomplete combustion and soot formation, which can dirty the cad-cell and result in high resistance readings.
  • Adjusting the barometric damper improperly can affect the combustion air flow, potentially causing sooting or operational problems with the burner that would affect the cad-cell readings.

Maintenance or troubleshooting to correct these issues should be carried out by a qualified technician to ensure safe and efficient operation of the burner system.