Final answer:
The rating of a three-phase transformer with a load current of 139.1A and a secondary voltage of 415V is calculated to be approximately 100 kVA, which is option (b).
Step-by-step explanation:
To calculate the rating of a transformer, you can use the following formula for a three-phase transformer: Rating (in VA) = √3 × V × I, where √3 is the square root of 3, V is the voltage, and I is the current.
In this case, the load current (I) is 139.1A, and the secondary voltage (V) is 415V. Plugging in the values, we get:
Rating = √3 × 415V × 139.1A = 1.732 × 415V × 139.1A ≈ 100 kVA
Therefore, the rating of the transformer would be 100 kVA, which corresponds to option (b).