Final answer:
The full-load primary current for the given transformer is 27.27 A, and the no-load current is approximately 0.182 A. The no-load current as a percentage of the full-load current is about 0.67%.
Step-by-step explanation:
To calculate the no-load current (Io) as a percentage of the full-load current (Ifl) for the given transformer, we first need to determine the full-load current on the primary side, since the transformer is rated at 300 kVA and 11 kV. The full-load primary current can be calculated using the formula:
Ifl = S / Vp
Where S is the apparent power (300 kVA) and Vp is the primary voltage (11 kV).
Using the formula, we get:
Ifl = 300,000 VA / 11,000 V = 27.27 A (Full-load current on the primary side)
The no-load current is found when the primary is energized without any load connected to the secondary. The magnetizing branch represented by Rc,p and Xm,p will draw the no-load current. Since we're dealing with a no-load condition, and the coil resistance and reactance are high, we can approximate that no-load current to be largely reactive and is calculated by:
Io = Vp / √(Rc,p^2 + Xm,p^2)
Plugging in the given values:
Io = 11,000 V / √(57,600,000^2 + 16,340,000^2) = 0.182 A
Finally, to find the no-load current as a percentage of the full-load current:
Percentage = (Io / Ifl) × 100 = (0.182 A / 27.27 A) × 100 ≈ 0.67%