when an existing two-wire, nongrounding-type receptacle is replaced in a location where the code requires a gfci receptacle, it is permitted to be replaced by .

User Medihack
by
7.6k points

1 Answer

1 vote

Answer:

A non-grounding receptacle can be replaced with a GFCI type receptacle. The receptacle shall be marked “No Equipment Ground”. An equipment grounding conductor shall not be connected from the GFCI type receptacle to any outlet supplied from the GFCI receptacle.