Answer:
Heat pump needs 1.965 megajoules each hour to run.
Step-by-step explanation:
The Coefficient of Performance (
), no unit, of a Carnot's heat pump is:
(1)
Where:
- Heat received by the building, measured in megajoules.
- Work needed to run the heat pump, measured in megajoules.
If heat pump is a Carnot engine working in reverse, then the amount of work needed to run the heat pump is the least possible work. If we know that
and
, then the amount needed by the heat pump each hour is:



Heat pump needs 1.965 megajoules each hour to run.