which of the following voltage and phase arrangements requires ground-fault protection of equipment for each service disconnecting means rated at 1,000 amperes or greater

User Pbathala
by
7.5k points

1 Answer

4 votes

Step-by-step explanation:

230.95 states that ground-fault protection of equipment shall be provided for solidly grounded wye electrical services of more than 150 volts to ground, but not exceeding 600 volts phase-to-phase for each service disconnecting means rated 1000 amperes or more.