181k views
5 votes
a balanced delta-connected load is supplied by a 60-hz three-phase source with a line voltage of 240 v. each load phase draws 6 kw at a lagging power factor of 0.8. find:

1 Answer

3 votes

Step-by-step explanation:

Line current: To find the line current, we can use the formula:

I = P / (√3 * V * cos(Φ))

where:

I = line current (A)

P = power per phase (W)

V = line-to-line voltage (V)

cos(Φ) = power factor (lagging, so cos(Φ) = 0.8)

Plugging in the values:

I = 6 kW / (√3 * 240 V * 0.8) = 20.5 A

Phase current: To find the phase current, we divide the line current by √3:

I_phase = I / √3 = 20.5 A / √3 = 11.7 A

Total power: To find the total power, we multiply the power per phase by 3:

P_total = 3 * 6 kW = 18 kW

Apparent power: The apparent power, S, can be found using the formula:

S = √(P^2 + Q^2)

where:

P = real power (W)

Q = reactive power (VAR)

To find the reactive power, Q, we can use the formula:

Q = P / tan(Φ) = P / tan(arccos(cos(Φ)))

Plugging in the values:

Q = 6 kW / tan(arccos(0.8)) = 7.5 kVAR

S = √(6 kW^2 + 7.5 kVAR^2) = √(36 + 56.25) kVA = 9 kVA

The results show that the balanced delta-connected load is supplied by a 60-Hz three-phase source with a line voltage of 240V and draws a total of 18 kW of real power at a lagging power factor of 0.8. The line current is 20.5 A and the phase current is 11.7 A. The apparent power is 9 kVA.

User Rob Quincey
by
7.9k points