Three parallel three-phase loads are supplied from a 480V (line-line RMS), 60 Hz three-phase supply. The loads are as follows: Load 1: A 20HP motor operating at full load, 90% efficiency and a 0.8 lagging power factor. Load 2: A balanced resistive load that draws a total of 20kW. Load 3: A Y-connected capacitor bank with a total rating of 20kVAr. What is the total system kW ?

User Tchar
by
7.1k points

1 Answer

4 votes

Answer:

The total system active power P = P_1 + P_2 + P_3 = 34.91 KW

Step-by-step explanation:

Load 1: Active power P_1 = 20 HP = 14.91kW;

Reactive power
Q1 = P tan(\phi)


= 14.91* tan(cos^(-)0.8) = 11.18 kvar

Load 2: Active power P_2 = 20 kW;

Reactive power Q2 = 0 since the load is purely resistive.

Load 3: Active power
P_3 = 0 due to purely capacitiveload

Reactive power
Q_3 = -20 Var

a) since all three loads are connected in parallel therefore

The total system active power P = P_1 + P_2 + P_3 = 34.91 KW

Total system reactive power Q = Q_1 + Q_2 + Q_3 = 11.18 + 0 -20 = -8.82 kVar

Since Q = 0, the power factor is unity.

Supply current per phase is given by


I = (P)/(√(3)V_(L))


= (34910)/(√(3)* 480) = 41.99 A