A 3-phase , 1MVA, 13.8kV/4160V, 60 Hz, transformer with Y-Delta winding connection is supplying a3-phase, 0.75 p.u. load on the 4160V side of the transformer. The load has leading power factor of 0.9. It issupplied by 1 p.u. voltage on the 13.8kV side. The transformer per unit impedance is j0.12 referred to thesecondary side.

a. Find the load impedance.
b. Find the input current on the primary side in real units.
c. Find the input power factor

User Zac Delventhal
by
3.2k points

1 Answer

24 votes
24 votes

Answer:

a) 23.89 < -25.84 Ω

b) 31.38 < 25.84 A

c) 0.9323 leading

Step-by-step explanation:

A) Calculate the load Impedance

current on load side = 0.75 p.u

power factor angle = 25.84


I_(load) = 0.75 < 25.84°

attached below is the remaining part of the solution

B) Find the input current on the primary side in real units

load current in primary = 31.38 < 25.84 A

C) find the input power factor

power factor = 0.9323 leading

attached below is the detailed solution