Final answer:
For the purpose of derating ampacity in a branch circuit raceway, only the insulated conductors are counted. Assuming the bare conductors are used for grounding and not counted, a total of 9 conductors would be considered (3 black, 3 white, and 3 red).
Step-by-step explanation:
The question asks how many conductors would be counted in a branch circuit raceway for the purposes of derating conductor ampacity. According to the National Electrical Code (NEC), any current-carrying conductors should be counted for ampacity derating. Bare conductors, if they are used for grounding, are typically not counted as current-carrying conductors. The conductors specified in the question can be summarized as follows:
- 3 bare conductors (not counted if used for grounding)
- 3 black insulated conductors (counted)
- 3 white insulated conductors (counted)
- 3 red insulated conductors (counted)
In this case, assuming the bare conductors are used for grounding, only the insulated conductors are counted for ampacity derating. Therefore, the answer is 9 conductors (3 black + 3 white + 3 red).