Final answer:
When the power factor falls to 0.866 lag, Wattmeter 1 reads 22 kW, and Wattmeter 2 reads 11 kW. For a power factor of 0.573 lag, Wattmeter 1 reads approximately 33.9 kW, and Wattmeter 2 reads approximately 10.1 kW.
Step-by-step explanation:
When using the two wattmeter method to measure balanced three-phase power, with each wattmeter initially reading 22 kW at unity power factor, the readings change as the power factor decreases while keeping total power the same.
At a power factor of 0.866 lag, the two wattmeters will have different readings due to the phase shift between the voltage and current. Assuming the angle φ corresponds to the power factor cos(φ), we calculate the angle as φ = cos-1(0.866), or 30 degrees. The power measured by each wattmeter can be determined by using the formula:
W1 = Total Power * (1 + cos(2 φ)) / 2
W2 = Total Power * (1 - cos(2 φ)) / 2
Since the total power is unchanged at 44 kW (22 kW from each wattmeter at unity power factor):
-
- (i) W1 at 0.866 lag = 22 kW * (1 + cos(60 degrees)) / 2 = 22 kW
-
- (ii) W2 at 0.866 lag = 22 kW * (1 - cos(60 degrees)) / 2 = 11 kW
When the power factor falls to 0.573 lag, the corresponding angle is φ = cos-1(0.573), or approximately 54 degrees. The wattmeter readings will again differ based on this angle:
-
- (iii) W1 at 0.573 lag = 22 kW * (1 + cos(108 degrees)) / 2 ≈ 33.9 kW
-
- (iv) W2 at 0.573 lag = 22 kW * (1 - cos(108 degrees)) / 2 ≈ 10.1 kW